Conductor material: Copper stranded
Conductor class: acc. to DIN VDE 0295 class 5, acc. to IEC 60228 5 Class,GB/T3956 Class 5
Core insulation: Special rubber compound HEPR -J-90-001
Core identification: Up to 5 cores acc. VDE 0293-308, from 6 black with white numbers and GNYE
Stranding: Stranded in layers
Shielding: Optional. Cables can be shielded individually or in pairs, e.g. 12 x 1 (C), i.e. 1 mm² individually or 6 x (2 x 1)C, i.e. 2 x 1 mm² in pairs and shielded.
Inner sheath material: Special rubber compound CPE-H-90-001
Anti-twist braid: Polyester braid
Outer sheath: Special rubber compound CPE-H-90-001
Jacket color: Black RAL5005; Yellow RAL1023
Rated voltage: 300/500V; 450/750V; 0.6/1 kV
Test voltage: 2kV; 2.5kV; 3.5kV
Current carrying capacity: acc. to DIN VDE 0298
Min. bending radius fixed: 10XD
Min. bending radius moved: 7.5XD
Minimum distance with S-shaped directional change: 20 X D
Operat. temp. fixed min/max: -40 °C / +90 °C
Operat. temp. moved min/max: -25 °C / +90 °C
Temp. at conductor: +90 °C
Torsion:± 50 °/m
Tensile load: 30N/mm2
Burning behavior: acc. to IEC 60332-1-2
Oil resistance: acc. EN 60811-2-1