Conductor material:
|
Bare copper strand
|
Conductor class:
|
Acc. to IEC 60228 cl. 5
|
Core insulation:
|
XLPE
|
Core identification:
|
Acc. to DIN VDE 0293-308 coloured cores with GNYE
|
Stranding:
|
Stranded in layers
|
Shield:
|
Alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned
|
Outer sheath:
|
Halogen-free compound
|
Sheath colour:
|
Black, RAL 9005
|
Rated voltage:
|
Uo/U 0,6/1 kV - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V
|
Testing voltage:
|
4 kV
|
Conductor resistance:
|
Acc. to IEC 60228 cl. 5
|
Insulation resistance:
|
Min. 200 MΩ x km
|
Capacity:
|
Look at the table on the right side
|
Min. bending radius fixed:
|
≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7,5 x d; > 20mm Ø: 10 x d
|
Min. bending radius moved:
|
≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d
|
Operat. temp. fixed min/max:
|
-40 °C / +80 °C
|
Operat. temp. moved min/max:
|
-15 °C / +70 °C
|
Temp. at conductor:
|
+ 90 °C in operation; +250 °C in case of short-circuit
|
Halogen free:
|
Halogen-free acc. to IEC 60754-1
|
Burning behavior:
|
Self-extinguishing & flame-retardant acc.to IEC 60332-1-2
|