Conductor material: bare copper wire
Conductor grade: according to DIN VDE 0295 Class 5 IEC 60228 Class 5.
Insulation: PVC
Core wire identification: in accordance with VDE 0293-308, at most 5 wires are colored, from 6 black wires with white numbers to 6 wires at most, with white and black numbers, with or without GNYE.
Stranding: parallel side by side
Outer sheath: special PVC
Sheath color: black RAL9005;
Rated voltage: uo/u 300/500 v.
Test voltage: 2KV
Conductor resistance: conforming to IEC 60228 cl. 5 standard.
Insulation resistance: 200 MΩ x km minimum.
Capacitance: core/core is about 120 nF/km;
Fixed minimum bending radius: according to DIN VDE 0298 Part 3.
Minimum bending radius movement: according to DIN VDE 0298 Part 3.
The minimum/maximum temperature level is fixed. -35°C/+70°C。
The temperature level moves by minimum/maximum. -25°C/+60°C。
Flame retardant grade: self-extinguishing and flame retardant, in line with IEC 60332-1 standard.
Standard: according to DIN EN 50214.
Product identification: AEIN Beike Shanghai AEIN Wire & Cable Co., Ltd. Model specification voltage CE