Product introduction
-
01 Product application Used for power, control and connection cables in power facilities for data and signal transmission. Laying methods are fixed laying, and mobile laying, no clear cable path, no tensile stress. Cable can be suitable for dry, wet and wet indoor.Shielded power, control and connection cables in electrical installations and handheld power tools, suitable for fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and damp rooms. Outdoor
use within the temperature range, not to be buried
-
02 Product characteristics • Enhanced oil resistance Special-PUR-outer jacket Resistant to acids, alkalis, solvents, hydrolysis, lubricants, etc.
• Free of paint-damaging substances and silicone (during the production process)
• Enhanced abrasion resistance, notch resistance, microbial resistance, cut resistance, tear resistance • UV and ozone resistant PUR outer jacket
-
03 Technical certification • Conform to RoHS
• Conform to 2014/35/EU-Guideline(" Low voltage Directive ")CE • We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Product structure
Conductor material: Bare copper fine wire stranding
Conductor class: In accordance with IEC 60228 cl. 5 standard
Insulation:PVC
Core identifier: In accordance with DIN VDE 0293 black core, white numbers, with GNYE, 3 cores
Stranding: Stranded in layers
Shielding: Tinned copper braid, covering approx. 85%
Outer sheath:PVC
Jacket color: Black RAL 9005 Or gray RAL7001
Rated voltage:300/500 V
Test voltage:2 kV
Conductor resistance: In accordance with IEC 60228 cl. 5 standard
Insulation resistance Small 20 MΩ xkm
Min. bending radius fixed:7.5 x d
Min. bending radius moved:15 x d
Operat. temp. fixed min/max:-40 °C / +80 °C
Operat. temp. moved min/max:-5 °C / +70 °C
Burning behavior:IEC 60332-1-2
Standard:VDE 0250- 204
Product identification:Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.,LTD Model number specification voltage CE Meter scale