Conductor material: bare copper wire
Conductor class: acc. to IEC 60228 cl. 5standard
Insulation:PE
Identification of core wire:< 0,5 mm²:5Core and below the use of color separation, in line withn. DIN 47100.5Multi-core cable above core adopts core separation , white ink dot distinguish; ≥ 0,5 mm²: 5Core and below use color separation, containing
yellow/Green line, matchn. DIN 47100.5Multi-core cable above the core adopts black core wire, white ink numbered to distinguish(If there are special requirements to customize)
Stranding: A pair of strands twisted in layers
Shielding layer:Foil in pairs(PiMf), adjacent to the tinned baffle wire.
Shielding layer:Tinned copper braid, coverage approx70%
Outer sheath:PVC-H-70-001
Jacket color: BlackRAL9005;greyRAL 7001
Rated voltage:0.5And below300/300V;0.5above300/500V
Test voltage:0.5And below1500V;0.5above2000V
Conductor resistance: YesDIN VDE 0812
Insulation resistance: minimum 5 GΩ x km
Capacitance: maximum 60 nF/km (from4Pair start)
Min. bending radius fixed:10 x d
Min. bending radius moved:15 x d
Operat. temp. fixed min/max:-15 ℃ / +80 °C
Operat. temp. moved min/max:-5 ℃/ +80 °C
Standard:DIN VDE 0812
Burning behavior:Self-extinguishing and flame retardant meetIEC 60332-1-2standard
Product identification:Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.,LTD Model number specification voltage CE Meter scale