Product introduction
-
01 Product application
The cable is suitable for permanent underwater operation where additional mechanical protection is required
-
02 Product characteristics
• Flame retardancy according to EN 60332-1-2; IEC 60332-1-2;
• Abrasion and tear resistance, oil and ozone resistance
• For special structure, other size, core wire and sheath color products can be customized.
-
03 Technical certification ·RoHS Compliant
·Complies with 2014/35/EU-Guidelines ("Low Voltage Directive") CE.
• We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Product structure
Conductor: DIN VDE 0295 standard class 6 soft stranded tinned copper conductor.
Inner conductor layer: special rubber material, semi-conductive.
Insulation: Type 3GI3 rubber.
Outer conductor layer: special rubber material, semi-conductive, easy to peel off.
Monitoring core (optional): copper conductor insulated with EPR.
Ground Wire: Tinned annealed copper helically wound.
Inner Sheath: Waterproof synthetic butyl rubber.
Armor: Galvanized steel wire braid.
Outer Sheath: Type 5GM5 Rubber.
Rated voltage: 0.6/1kV
Test cable: 2500V
Conductor resistance: in accordance with IEC 60228 standard
Temperature class Fixed: -40°C / +90°C
Temperature Rating Mobile: -15°C / +90°C
Flammability rating: IEC 60332-1-2
Standard: VDE 0250 Part 813
Marking: Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.,LTD Model Specification Voltage CE Meter Mark