Product introduction
-
01 Product application
The cable is used in buildings or industrial buildings with dense personnel or valuables; Cannot be directly buried or installed in water; It can only be laid outdoors when it is protected from direct sunlight and other external influences.
-
02 Product characteristics
Flame retardant in accordance with IEC 60332-1-2
Non-delay performance in accordance with IEC 60332-3-24
Halogen-free according to IEC 60754-1:2011(Total halogen acid gas)
Combustion gas corrosivity in accordance with IEC 60754-2:2011(acidity)
Low smoke density in accordance with IEC 61034-2:2005+A12013+A2:2020
-
03 Technical certification
· Comply with RoHS standards
· Comply with Directive 2014/35/EU-Guideline (" Low Voltage Directive ")CE
Product structure
Conductor material: bare copper wire
Conductor class: According to IEC 60228 cI.5 standard cI.2 Optional
Insulation :XLPE
Core identifier: two cores red and blue; three core red yellow green; Four core red yellow green blue; Five core red yellow green blue yellow/green
Stranding: stranding in layers
Shielding: Copper wire braid shielding tinning wire is optional
Outer sheath: halogen-free, thermoplastic polyolefin mixture
Jacket color: black, RAL 9005 or grey RAL 7001
Rated voltage :0.6/1kV
Test voltage :3.5kV
Conductor resistance: According to IEC 60228 cI.5 standard
Small bending radius fixed :7.5 x d
Small bending radius movement :15 x d
Temperature rating fixed :-15°C/+90 °C
Temperature rating shift :-5°C/+90°C
Flame retardant rating :IEC 60332-1-2
Standard :HD 603-3G IEC60502
Product identification: Aein bei Ke SHANGHAI AEIN WIRE & CABLE CO.LTD Model Specification Voltage CE meter standard