Conductor material: bare copper wire
Fireproof conductor mica tape wrapped
Conductor class: According to IEC 60228 cI.5 cI.2 Optional
Insulation :XLPE
Jacket: halogen-free, thermoplastic polyolefin mixture
Core identification: two cores red and blue; Three core red yellow green; Four core red yellow green blue; Five core red yellow green blue yellow/green
Jacket color: Black RAL 9005 or grey RAL 7001
Stranding: stranding in layers
Rated voltage :0.6/1kV
Test voltage: 3.5kV
Conductor resistance: According to IEC 60228 cI.5
Conductor rated temperature :90°C
Small bending radius fixed :7.5 x d
Small bending radius movement :15 x d
Fixed temperature: -25℃/+90°C
Moving temperature :-25°C/+90°C
Conductor operating temperature: normal operation 90°C, short circuit (long duration does not produce 5 seconds)250°C
Standard: HD 603-3G IEC60502-1
Fire resistance :EN 50200, EN 50362, IEC 60331-1 and 2(PH120- at least 120 minutes, 842°C)(These cables are exposed to the effects of fire, but maintain the integrity of power and circuits and equipment, at 830-870°C for at least 120 minutes)
Flame retardant reaction :Cca-s1b, d1, a1 (EN 50575:2014+A1:2016)
Flame retardant :EN 60332-1-2; IEC60332-1(H≤425mm)
Flame retardant :EN50399 (Flame source :20,5 kW; Fs≤2 m)
Low heat :EN50399 (flame source :20,5 kW)
Total heat release :HRR≤60 kW
Temperature indicator: FIGRA≤300 W/s
Low yield and opacity of emission smoke (s1b):
s1: Total flue gas production (TSP)<50㎡ and peak flue gas release (peak SPR)≤0.25㎡/s
s1b:s1+60%< transmittance <80%(UN EN 61034-2; IEC 61034-2)
Low yield of combustion droplets (d1):
d1: No burning droplets/particles lasting more than 10 'within 1200'. (EN 50399 - Flame source :20.5kW):
Low acidity and conductivity of emission gases:
a1: pH≥4, conductivity <2,5 μS/mm
(EN 60754-2; EC 60754-2)
Product identification: Aein bei ke SHANGHAI AEIN WIRE & CABLE CO.LTD Model Specification Voltage CE meter standard