Conductor material: Bare copper
Conductor class: acc. to UL758 Standard,ASTM B3 or ASTM B33 standard.VDE 0295 5 class conductor pt.4 or. IEC60228 class 5 conductor pt.4
Core insulation:PVC,XLPE,TPE optional
Core identification: acc. to DIN VDE 0293 Black with white numbering,1 x GNYE
Stranding: Stranded in layers
Shielding: Tinned copper wire braid, shielding density>70%
Outer sheath: PUR
Jacket color: gray RAL 7001 or black RAL 9005
Rated voltage:1000 V
Test voltage:3 kV
Conductor resistance:UL1581 ASTM class C
Insulation resistance PVC:+20 °C ≥ 20 MΩ x km;PVC:+20 °C ≥ 200 MΩ x km
Min. bending radius fixed:4x d
Min. bending radius moved:7.5x d
Operat. temp. fixed min/max:-40 °C / +80 °C
Operat. temp. moved min/max:-30 °C / +80 °C
Burning behavior: Self-extinguishing and flame retardant meet FT2
Oil resistance:UL1581:IRM 902; acc. to DIN EN 60811-2-1
Approvals:UL&CUL:UL1032,UL10914,UL11122,UL3237,UL3820,UL21320
CE: If needed CE Certification or halogen-free requirements shall be indicated separately
Product identification: E503807 ® AWM Model number specification temperature voltage VW-1 or ® AWM I A specification temperature voltage FT2