Conductor material: Bare copper or tinned copper
Conductor type: In accordance with UL 758 Standard, ASTM B3 or ASTM B33 Standard, DIN VDE 0295 5 Conductor or. IEC 60228 5 Conductor
Core insulation:PVC,HDPE
Core identification:< 20AWG:5 cores and below are distinguished by color separation, acc. to Din 47100, multi-core cables above 5 cores are distinguished by core wire color separation, and white ink is used for distinction;≥20AWG:
5 cores and below are distinguished by color separation, including yellow/ Green ground wire, acc.to Din 47100, multi-core cables with more than 5 cores use black core wires, and white ink numbers are used to distinguish them. (customized upon request if there are special requirements)
Stranding: cores resp. bundles parallel side by side
Sheath:PVC
Jacket color: Gray RAL7001 Or black RAL9005
Rated voltage:300V
Test voltage:2.0 kV
Conductor resistance:UL1581 ASTM class C
Insulation resistance:PVC:+20 °C ≥ 20 MΩ x km;HDPE:+20 °C ≥ 200 MΩ x km
Min. bending radius fixed:7.5x d
Min. bending radius moved:15x d
Operat. temp. fixed min/max:-15 °C / +80°C
Operat. temp. moved min/max:-5°C / +80°C
Burning behavior: Self-extinguishing and flame retardant UL1581 VW-1;CSA C22.2 No.2556-15 FT1,FT2;IEC 60332-1-2 standard
Approvals: UL&CUL:UL1007,UL1569,UL10450,UL2464
CE:LiYY,Li2YY If neededCECertification requirements should be specified separately
Product identification:Aein bei ke E503807 ® AWM Model number specification temperature voltage ® AWM Ⅰ/Ⅱ A/B specification temperature voltage FT2 SHANGHAI AEIN Meter scale